18 INTEGRA 128-WRL SATEL
expanders must be independently supplied (by means of a separate cable from the control
panel, expander with power supply, or a power supply unit). Where the distance between the
control panel and the modules exceeds 300 m, the modules without power supply unit should
not be supplied from the control panel. They should have an independent supply source
(a power supply unit or an expander with power supply).
3.6.1 Addressing devices connected to expander bus
Each module to be connected to the expander bus must have its own individual address from
the 0 to 31 range (the addresses must not repeat). It is recommended that consecutive
addresses be assigned starting from 0. This will allow you to avoid problems during
expansion of the system (e.g. changing numeration of zones or outputs due to connection of
a new expander). The addresses should be set by means of DIP-switches situated on
expander electronics board. The expander addresses are displayed on the keypad in
hexadecimal format (from 00 to 1F).
100 m
2EOL/NC
NC TMP COM
12V
NC TMP
2EOL/NC
NC TMP COM
12V
NC TMP
2EOL/NC
NC TMP COM
12V
NC TMP
INTEGRA 128-WRL
CA-64 E CA-64 E CA-64 E
Fig. 12. Connection of modules without power supply to the control panel when the distance
between panel and modules is small (by the example of CA-64 E zone expander).
Several modules (connected in parallel) are connected to the control panel lead-in.
Expanders only may be connected to the +EX power terminal. Detectors must be supplied
by separate power leads.