SATEL Installer Manual 17
number of wires in signal cable
distance between module and control panel CK DT COM
up to 300 m 1 1 1
300 – 600 m 2 2 2
600 – 1000 m 2 2 4
Table 3.
Note: Signal wires (DT, CK and COM) must be run in one cable!
INTEGRA 128-WRL
CA-64 E
Fig. 10. Connection of modules without power supply unit, by the example of CA-64 E zone
expander. The expander is mounted in the same housing as the control panel, hence the
TMP terminal is shorted to the COM ground.
INTEGRA 128 WRL CA-64 EPS
18 V AC ±10%
Fig. 11. Connection of expansion module with power supply unit, by the example of
CA-64 EPS zone expander. Housing tamper contact is connected to TMP and COM
terminals. AC terminals should be connected to transformer secondary winding terminals.
The modules without power supply unit may be powered directly from the control panel if the
distance between control panel and module is not higher than 300 m. Where distances are
small (up to 100 m), the modules without power supply unit may be connected one after the
other to one supply cable (see: Fig. 12). If this is the case, devices connected to the